Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1136538.015
Citation: 01002
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,000.00
Current Penalty: $1,800.00
Issuance Date: 07/25/2016
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 07/29/2016
Gravity: 1
Report ID: 0625400
Contest Date:
Final Order: 08/12/2016
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/12/2016 | $1,800.00 | 07/29/2016 | Serious | |
Penalty | Z: Issued | 07/25/2016 | $3,000.00 | 07/29/2016 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about March 31, 2016 and in times prior thereto, the following electrical devices were not identified. This condition created an electrical hazard to rebar fabricators. a. 120/240 volt breaker panel did not have the breakers labeled as to their purpose, located on the wall in front of the fabrication shop b. Rod Chomper Model CRE8D stop button was replaced by toggle switch and not identified.