Violation Detail
Standard Cited: 5A0001 OSH Act General Duty Paragraph
Inspection Nr: 1128552
Citation: 01002
Citation Type: Serious
Abatement Status: X
Initial Penalty: $1,875.00
Current Penalty: $1,700.00
Issuance Date: 01/03/1992
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 08/31/1992
Gravity: 04
Report ID: 0336000
Contest Date: 01/27/1992
Final Order: 07/13/1992
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 07/13/1992 | $1,700.00 | 08/31/1992 | Serious | |
| Penalty | Z: Issued | 01/03/1992 | $1,875.00 | 02/06/1992 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard: ELECTRIC
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards due to the ignition of flammable vapor/gases from unclassified electrical installations:: (a) Platformer Unit Control Room; control room ventilation air intake system did not prevent the entrance of flammable vapor/gases, such as, but not limited to, naptha and hydrogen. The fresh air intake duct was located approximately 29'9" above grade.