Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1787983.015
Citation: 01001E
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/30/2025
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 05/06/2025
Gravity: 10
Report ID: 0111700
Contest Date: 06/11/2025
Final Order: 08/25/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/25/2025 | $0.00 | 05/06/2025 | Serious | |
Penalty | C: Contested | 06/12/2025 | $0.00 | 05/06/2025 | Serious | |
Penalty | Z: Issued | 04/30/2025 | $0.00 | 05/06/2025 | Serious |
Text For Citation: 01 Item/Group: 001E Hazard:
29 CFR 1910.335(a)(1)(i): Employees were working in areas where there were potential electrical hazards and were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a. Site- On or about November 12, 2024, an employee operating an aerial device near energized secondary powerlines operating at up to 240 volts and energized primary powerlines operating at up to 34.5kv was not protected from electric shock where insulated gloves and sleeves were not worn. b. Site- On or about November 12, 2024, an employee operating an aerial device near energized primary powerlines operating at up to 34.5kv was not protected from burns where protective clothing for the upper and lower body, rated for the arc flash potential that they were exposed to, was not worn.