Violation Detail
Standard Cited: 19100119 D03 I E Process safety management of highly hazardous chemicals.
Inspection Nr: 1702519.015
Citation: 01001E
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/10/2024
Nr Instances: 1
Nr Exposed: 15
Abatement Date: 05/01/2025
Gravity: 5
Report ID: 0316700
Contest Date:
Final Order: 05/02/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/02/2024 | $0.00 | 05/01/2025 | Serious | |
Penalty | Z: Issued | 04/10/2024 | $0.00 | 05/28/2024 | Serious |
Text For Citation: 01 Item/Group: 001E Hazard:
29 CFR 1910.119(d)(3)(i)(E): The employer did not have a compilation of written process safety information pertaining to the ventilation system design. a. The Old System - On or about October 11, 2023, the employer failed to develop and document the emergency ventilation system design. Failure to ensure the ventilation system design is adequate can result in IDLH concentrations of ammonia to accumulate, fires, and the emergency response personnel being exposed to dangerous levels of ammonia in the event on a release. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.