Violation Detail
Standard Cited: 19100307 D Hazardous (classified) locations.
Inspection Nr: 771461.015
Citation: 01001D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/03/2013
Nr Instances: 4
Nr Exposed: 4
Abatement Date: 06/24/2013
Gravity: 10
Report ID: 0626300
Contest Date:
Final Order: 08/09/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/09/2013 | $0.00 | 06/24/2013 | Serious | |
| Penalty | Z: Issued | 06/03/2013 | $0.00 | 06/24/2013 | Serious |
Text For Citation: 01 Item/Group: 001D Hazard:
29 CFR 1910.307(d): All conduits were not threaded and made wrench-tight: The employer does not ensure that conduits in hazardous areas are made wrench-tight. This violation was discovered on January 17, 2013, where 3/4-inch flexible metal conduit and 1-inch electrical metallic tubing were not made wrench-tight in areas where saw dust had accumulated: a) In the Sawyer and Gang Saw operations area, electrical metallic conduit connected to an Eaton, Cutler - Hammer electrical disconnect, 30 amp 600 VAC/60 Hz/ 250VAC; b) In the Saw Bearer and electrical service area, electrical metallic conduit connected to Allen Bradley electrical disconnects, Model No.: 1K1200-200AMP-300AMP, Serial No.: NYP7 38; c) In the Edgers work area, electrical metallic conduit connected to an Eaton, Cutler - Hammer electrical disconnect, 30 amp 600 VAC/60 Hz/ 250VAC Model No. / Serial No. N/A; d) In the area of the C Frame conveyor, 3/4-inch flexible metal conduit providing power to a Toshiba 480V/600Hz electric motor.
Translate