Violation Detail
Standard Cited: 19100134 I07 Respiratory Protection.
Inspection Nr: 1731471.015
Citation: 01001D
Citation Type: Serious
Abatement Date: 08/09/2024
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/16/2024
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC):
Gravity: 5
Report ID: 0213900
Contest Date: 08/06/2024
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 09/09/2024 | $0.00 | 08/09/2024 | Serious | |
Penalty | Z: Issued | 07/16/2024 | $0.00 | 08/09/2024 | Serious |
Text For Citation: 01 Item/Group: 001D Hazard:
29 CFR 1910.134(i)(7):Oil lubricated compressor(s) used to supply breathing air did not have a high-temperature or carbon monoxide alarm(s) or both: a) Pinewald Aqua water tower inside of outdoor containment area: A gas detection system to monitor carbon monoxide levels was not installed on the filtration unit providing compressed air to the RPB Nova 3 air blasting hoods from the Atlas Copco XAS 1800 JD air compressor for employees sandblasting within the containment area, on or about 4/9/24. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.