Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1291440.015
Citation: 01001D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/25/2018
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 07/31/2018
Gravity: 10
Report ID: 0521700
Contest Date: 07/25/2018
Final Order: 04/17/2019
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 04/17/2019 | $0.00 | 07/31/2018 | Serious | |
| Penalty | C: Contested | 08/17/2018 | $0.00 | 07/31/2018 | Serious | |
| Penalty | Z: Issued | 07/25/2018 | $0.00 | 07/31/2018 | Serious |
Text For Citation: 01 Item/Group: 001D Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a. On or about January 31, 2018 through February 16, 2018, in the production room, two Patterson 30 H30B-CS high velocity fans were used where flammable vapors were present and were not intrinsically safe, approved for a Class I hazardous location, or safe for a Class I hazardous location.