Violation Detail
Standard Cited: 19100119 J04 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 993386.015
Citation: 01001C
Citation Type: Other
Abatement Date: 04/16/2015 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/02/2015
Nr Instances: 8
Nr Exposed: 29
Related Event Code (REC):
Gravity:
Report ID: 0213400
Contest Date: 03/24/2015
Final Order: 07/13/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | R: Review Commission | 07/13/2015 | $0.00 | 04/16/2015 | Other | |
Penalty | C: Contested | 03/25/2015 | $0.00 | 04/16/2015 | Serious | |
Penalty | Z: Issued | 03/02/2015 | $0.00 | 04/16/2015 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that was performed on process equipment wherein the documentation identified the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test: a) 125 Factory Ln, Middlesex, NJ site - Process area: Employer failed to document each inspection and test that was performed on the (8) pressure relief valves located on the Still #5 - fractional distillation column and molecular sieve. Condition noted on or about 02/05/15.