Violation Detail
Standard Cited: 19100119 D03 I H Process safety management of highly hazardous chemicals.
Inspection Nr: 913690.015
Citation: 01001C
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/05/2013
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 12/03/2013
Gravity:
Report ID: 0420600
Contest Date:
Final Order: 12/02/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/02/2013 | $0.00 | 12/03/2013 | Other | |
| Penalty | Z: Issued | 11/05/2013 | $0.00 | 12/03/2013 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.119(d)(3)(i)(H): Process safety information pertaining to the equipment in the process did not include the safety systems: a) For the Airgas covered process at 6601 E. 14th Ave., Tampa, FL, as observed on or about 08/12/2013, process safety information on the emergency stop system for propylene bulk tanks was not present in the process safety information compiled by the employer. The emergency stop system included two separate shutoff switches, an electrical push button, a nitrogen tank, pneumatic tubing/pipe for the nitrogen, an electrical to pneumatic/pressure signal converter, and emergency shutoff valves labeled PV1 through PV6 on the process and instrumentation diagram. No technical information on this system or its components was available and compiled in the employer's process safety information.