Violation Detail
Standard Cited: 19100178 C02 VI A Powered industrial trucks.
Inspection Nr: 1731103.015
Citation: 01001C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,067.00
Current Penalty: $0.00
Issuance Date: 08/22/2024
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 10/15/2025
Gravity: 5
Report ID: 0523300
Contest Date: 09/17/2024
Final Order: 01/27/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 01/27/2025 | $0.00 | 10/15/2025 | Serious | |
| Penalty | C: Contested | 09/18/2024 | $8,067.00 | 09/13/2024 | Serious | |
| Penalty | Z: Issued | 08/22/2024 | $8,067.00 | 09/13/2024 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.178(c)(2)(vi)(a): The employer did not provide powered industrial trucks designated as EX for use in an atmosphere in which combustible dust is or may be in suspension continuously, intermittently, or periodically under normal operating conditions, in quantities sufficient to produce explosive or ignitable mixtures, or where mechanical failure or abnormal operation of machinery or equipment might cause such mixtures to be produced. a) On or about February 28, 2024, the employer did not ensure that powered industrial truck(s) used in the Back Dump Area were designated as EX for use in an atmosphere in which combustible dust, such as but not limited to dried milk powder, was in suspension continuously, intermittently, and/or periodically under normal operating conditions. b) On or about March 1, 2024, the employer did not ensure that powered industrial truck(s) used in the Main Production Area were designated as EX for use in an atmosphere in which combustible dust, such as but not limited to dried milk powder, was in suspension in quantities sufficient to produce explosive or ignitable mixtures during blowdown events.