Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1396182.015
Citation: 01001C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,210.00
Current Penalty: $0.00
Issuance Date: 07/03/2019
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 07/30/2019
Gravity: 10
Report ID: 0522000
Contest Date:
Final Order: 07/24/2019
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/24/2019 | $0.00 | 07/30/2019 | Serious | |
| Penalty | Z: Issued | 07/03/2019 | $10,210.00 | 07/30/2019 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. a)On or about 4/22/2019 the employer did not properly mark circuit breakers located in the Line Bar Building to identify each electrical breaker for its intended purpose.