Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1268278.015
Citation: 01001C
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/17/2018
Nr Instances: 1
Nr Exposed: 11
Abatement Date: 04/30/2018
Gravity: 5
Report ID: 0317700
Contest Date: 04/27/2018
Final Order:
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 04/27/2018 | $0.00 | 04/30/2018 | Serious | |
Penalty | Z: Issued | 04/17/2018 | $0.00 | 04/30/2018 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." The employer does not ensure that circuit breakers used as switches in 120-volt and 277-volt fluorescent lighting circuits are listed and marked "SWD". This violation was most recently observed on or about October 18, 2017 at a worksite at 19 Bailey Street, Plains Township, PA, (East wall, In-Process Rm) when employees turned fluorescent lights on or off by cycling circuit breakers that were not manufactured or marked for switching duty (SWD). Abatement Certification Required