Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100334 C02 Use of equipment.

Inspection Nr: 987396.015

Citation: 01001B

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $7,000.00

Current Penalty: $0.00

Issuance Date: 09/29/2014

Nr Instances: 1

Nr Exposed: 3

Abatement Date: 10/03/2014

Gravity: 10

Report ID: 0111700

Contest Date:

Final Order: 10/24/2014

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 10/24/2014 $0.00 10/03/2014 Serious  
Penalty Z: Issued 09/29/2014 $7,000.00 10/03/2014 Serious  

Text For Citation: 01 Item/Group: 001B Hazard:

29 CFR 1910.334(c)(2): Test instruments and equipment and all associated test leads, cables, power cords, probes, and connectors were not visually inspected for external defects and damage before the electric equipment was used: a. High Voltage Cage, Lab 2- Employees were not protected from electric shock hazards where the employer failed to ensure that a CPS HPV-250 high voltage probe was inspected for external defects and damage before each use. On or about July 29, 2014 an unqualified employee sustained an electric shock while voltage testing a power supply producing up to approximately 8900 volts DC. The employee was using the CPS HPV-250 high voltage probe that was modified by the employer by adding a lead that connects the probe tip to the test point. The employee contacted the lead with their hand and received an electric shock.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close