Violation Detail
Standard Cited: 19100107 E09 Spray finishing using flammable and combustible materials.
Inspection Nr: 915140.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/30/2013
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 08/23/2013
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 08/26/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/26/2013 | $0.00 | 08/23/2013 | Serious | |
| Penalty | Z: Issued | 07/30/2013 | $0.00 | 08/23/2013 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.107(e)(9): 29 CFR 1910.107(e)(9): Flammable or combustible liquids for use in spraying operations were transferred from one container to another without both containers being effectively bonded and grounded to prevent discharge sparks of static electricity: a) Flammable wash booth - A 55 gallon drum of EXXSOL D60 Fluid, a class III combustible solvent (dearomatized hydrocarbons), was not electrically grounded. On or about 6/27/13. b) Flammable wash booth - When dispensing EXXSOL D60 Fluid, a class III combustible solvent (dearomatized hydrocarbons) from a 55 gallon drum into a five gallon bucket for use, the two containers were not electrically connected (bonded). On or about 6/27/13. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Translate