Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
Inspection Nr: 578180.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 11/30/2012 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/02/2012
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0317700
Contest Date:
Final Order: 10/31/2012
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/31/2012 | $0.00 | 11/30/2012 | Serious | |
Penalty | Z: Issued | 10/02/2012 | $0.00 | 11/01/2012 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(d)(4)(i): Openings to other rooms or buildings were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area shall be at least 4 inches below the surrounding floor: a) Paint storage room: The doorway from the storage room was not provided with a liquid tight raised sill or ramp which permitted spilled flammable bronzing fluid to leak outside of the storage room, as observed on or about August 16, 2012. Abatement Certification Required.