Violation Detail
Standard Cited: 19100119 F01 IIIB Process safety management of highly hazardous chemicals.
Inspection Nr: 315028167
Citation: 01001B
Citation Type: Serious
Abatement Status: X
Initial Penalty:
Current Penalty:
Issuance Date: 05/27/2011
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 07/13/2011
Gravity: 05
Report ID: 1032500
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
Text For Citation: 01 Item/Group: 001B Hazard: CHEMNEP
29 CFR 1910.119(f)(1)(iii)(B): The employer's written operating procedures covering safety and health considerations did not address the precautions necessary to prevent exposure, including engineering controls and administrative controls: a.)Oil Removal Procedure from Ammonia Refrigeration System did not include the location of nearest eye wash/shower facility, check the ventilation fans available in the area, assemble equipment needed such as a clean bucket to drain oil, necessary hand tools/ wrenches, and clear precautions such as slowly open the oil drain valve until a flow of oil starts. Note: Abatement certification is required for this item.