Violation Detail
Standard Cited: 19100106 D04 III Flammable liquids.
Inspection Nr: 1861490.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/22/2026
Nr Instances: 1
Nr Exposed: 80
Abatement Date: 04/30/2026
Gravity: 5
Report ID: 0134000
Contest Date:
Final Order: 02/24/2026
Related Event Code (REC): C
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/24/2026 | $0.00 | 04/30/2026 | Serious | |
| Penalty | Z: Issued | 01/22/2026 | $0.00 | 02/26/2026 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, was not approved for general use. Location: Warehouse B, Room 141 a) On or about 11/25/25, the employer did not ensure that electrical equipment installed in a flammable or combustible liquid storage room was approved for inside storage rooms with Category 2 and 3 flammable liquids. Both category 2 flammable liquids and category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C) were found stored in a storage room that had general use wiring.