Violation Detail
Standard Cited: 19260405 B01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1739491.015
Citation: 01001B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/11/2024
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 09/17/2024
Gravity: 5
Report ID: 0521700
Contest Date:
Final Order: 10/07/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/07/2024 | $0.00 | 09/17/2024 | Other | |
| Penalty | Z: Issued | 09/11/2024 | $0.00 | 09/17/2024 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasion. a) On or about April 4, 2024, at the above addressed jobsite, conductors of the SO cable providing 480-volt 30-amp 3 phase power to electrical equipment in use by employees, were not protected from abrasion when entering a cabinet, thereby exposing employees to electrical hazards.