Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 1671604.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/01/2023
Nr Instances: 1
Nr Exposed: 30
Abatement Date: 12/08/2023
Gravity: 5
Report ID: 0521400
Contest Date:
Final Order: 11/22/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/22/2023 | $0.00 | 12/08/2023 | Serious | |
Penalty | Z: Issued | 11/01/2023 | $0.00 | 12/08/2023 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(d)(4)(iv): Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. If a mechanical exhaust system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhaust outlet from the room, shall be on the exterior of the building in which the room is located. On or about July 28, 2023, and prior, the employer did not ensure that the ventilating equipment and the lighting fixtures in the room were operated by the same switch and located outside of the door. The employees are exposed to fire hazards from flammable chemicals vapor emissions. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).