Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1460709.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 05/08/2020
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 06/08/2020
Gravity: 10
Report ID: 0521400
Contest Date:
Final Order: 06/03/2020
Related Event Code (REC): A;R
Emphasis:
Substance: 1060
Substance: 1560
Substance: 2310
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/03/2020 | $0.00 | 06/08/2020 | Serious | |
Penalty | Z: Issued | 05/08/2020 | $0.00 | 06/08/2020 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 degree F (37.8 degree C), were dispensed into containers without the containers being electrically interconnected: On or about January 28 2020, three employees (temporary and permanent) were exposed to explosion and/or fire hazards that resulted in second degree burns to the hands, arms, and face when a High Speed Line operator manually picked up an unbounded and ungrounded plastic 55-gallon drum to transfer a flammable windshield car cleaning product (TBS-C15A) to another unbounded, ungrounded plastic 55-gallon drum (back drum). The employer did not ensure that adequate precautions were taken to prevent the ignition of flammable vapors from sources such as, but not limited to, static electricity. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).