Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
This violation item has been deleted.
Inspection Nr: 1434554.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 05/01/2020
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/07/2020
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): C
Gravity: 5
Report ID: 0317300
Contest Date:
Final Order: 05/15/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/15/2020 | $0.00 | 05/01/2020 | Serious | |
Penalty | Z: Issued | 04/07/2020 | $0.00 | 05/01/2020 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: a) 16941 Sussex Highway, Bridgeville, DE- On or about October 8, 2019, the employer failed to ensure that intrinsically safe electrical equipment was installed in the spray area. The electrical outlets that were located within ten feet of the spray application process were not rated for Class I, Division 2 locations.