Violation Detail
Standard Cited: 19260960 C01 III A
Inspection Nr: 1338194.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/07/2019
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 02/01/2019
Gravity: 10
Report ID: 0418800
Contest Date:
Final Order: 02/05/2019
Related Event Code (REC):
Emphasis:
Substance: 8870
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/07/2019 | $0.00 | 02/01/2019 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1926.960(c)(1)(iii)(A): Employees were not insulated from energized parts through the use of rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (c)(2) of this section: On or about August 4th, 2018, at the jobsite located at 3007 Yamato Rd. Corner of St. Andrew Blvd. Boca Raton, FL 33434, on a new installed wooden Pole # 769938508, the employer failed to ensure an employee used serviceable outer protector gloves with inner dielectric gloves to maintain a minimum approach distance of 3.71 feet while pulling a live electrical wire of 76.2KV, thus exposing the worker to an electrocution hazard. NOTE: ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED FOR THIS VIOLATION.