Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1334986.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/11/2019
Nr Instances: 2
Nr Exposed: 2
Abatement Date:
Gravity: 10
Report ID: 0521100
Contest Date:
Final Order: 01/24/2019
Related Event Code (REC): A;R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/24/2019 | $0.00 | Serious | ||
| Penalty | Z: Issued | 01/11/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.307(c)(2)(i): Equipment shall be approved not only for the class of location, but also for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that will be present: (Note to paragraph (c)(2)(i) of this section: NFPA 70, the National Electrical Code, lists or defines hazardous gases, vapors, and dusts by "Groups" characterized by their ignitable or combustible properties.) a) On or about July 31, 2018, the Shanghai Shengli Machinery Manufacture Co., Ltd. Mixer(LHY-0.5) EX-Factory No:2013111801 (17 cubic foot mixer), in the Mixing Room, and its associated electrical system were not approved for Class 2, Division 1 operations and not approved for usage with Magnesium (Combustible Metals) Powder. b) On or about July 31, 2018, the electronic platform scale in the Weighing Area used for weighing batch amounts of Magnesium Powder and its associated electrical system were not approved for Class 2, Division 1 operations and not approved for usage with Magnesium (Combustible Metals) Powder.
Translate