Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1334712.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,544.00
Current Penalty: $0.00
Issuance Date: 10/12/2018
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 02/01/2019
Gravity: 5
Report ID: 0317900
Contest Date:
Final Order: 11/05/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/05/2018 | $0.00 | 02/01/2019 | Serious | |
Penalty | Z: Issued | 10/12/2018 | $5,544.00 | 10/29/2018 | Repeat |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a) Orefield Cold Storage & Distribution Center, Inc. - On or about August 1, 2018, the employer did not document that the door entrance from the maintenance room into the compressor / engine room complies with their chosen recognized and generally accepted good engineering practices of IIAR 2, in that the door is not tight fitting and does not meet requirements of IIAR 2- 1999 section 6.3.1.5. Orefield Cold Storage & Distribution Center, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.119(d)(3)(ii), which was contained in OSHA inspection number 1188179, citation number 01, item number 01a, and was affirmed as a final order on July 13, 2017, with respect to a workplace located at 3824 Route 309, Orefield, PA 18069.