Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1281827.015
Citation: 01001B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/12/2018
Nr Instances: 1
Nr Exposed: 14
Abatement Date: 03/07/2018
Gravity:
Report ID: 0627700
Contest Date:
Final Order: 03/13/2018
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/13/2018 | $0.00 | 03/07/2018 | Other | |
| Penalty | Z: Issued | 02/12/2018 | $0.00 | 03/07/2018 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container: On or about December 6, 2017, and at times prior thereto, in the paint areas paint thinner having flashpoint of 39 degrees F was dispensed into a smaller container without being effectively grounded and bonded to electrically interconnect the containers to prevent static discharge during dispensing operation exposing employees to a fire hazard.