Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1270859.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/27/2018
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 03/30/2018
Gravity: 10
Report ID: 0112300
Contest Date:
Final Order: 03/23/2018
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/23/2018 | $0.00 | 03/30/2018 | Serious | |
Penalty | Z: Issued | 02/27/2018 | $0.00 | 03/15/2018 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected. Facility: On or about October 26, 2017 and at times prior thereto employees in the batch making area dispensed flammable liquids such as but not limited to Isopropanol Blend, Acetone Blend, and Acetone/Acetone Rework from metal 55 gallon drums through a plastic drum faucet into containers that were not bonded and grounded.