Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1168035.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/20/2016
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 09/29/2016
Gravity: 5
Report ID: 0524700
Contest Date:
Final Order: 10/06/2016
Related Event Code (REC): C
Emphasis:
Substance: 2037
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/06/2016 | $0.00 | 09/29/2016 | Serious | |
Penalty | Z: Issued | 09/20/2016 | $0.00 | 09/29/2016 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were not be dispensed into containers unless the nozzle and container were electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with. a. Forest City Technologies, Inc. located in Wellington, Ohio: On or about July 22, 2016, the employer did not ensure employees using a flammable liquid primer to wash the residue from the inside of a storage tank located in Plant 4, bonded the dispensing container to the storage tank prior to dumping the flammable primer into the tank. b. Forest City Technologies, Inc. located in Wellington, Ohio: On or about July 22, 2016, the employer did not ensure employees dispensing a flammable liquid primer into a 5 gallon bucket, grounded the storage drum to the bucket prior to transferring the liquid.