Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1132512.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/01/2016
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0317700
Contest Date:
Final Order: 08/24/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/24/2016 | $0.00 | Serious | ||
| Penalty | Z: Issued | 08/01/2016 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws. a) Northwest Wall, Aluminum Damper Department, 450 Riverside Drive, Wyalusing, PA - A Stone Saw Co., Incorporated Stone Saw (Serial No. 0307) was powered with a strained electrical cable that did not allow the male end to sit flush with the upper outlet receptacle of a mounted receptacle box exposing employees to electric arc flash hazards, as observed on or about March 15, 2016.