Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1119454.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 04/29/2016
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/05/2016
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0830600
Contest Date: 04/27/2016
Final Order: 04/28/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/28/2017 | $0.00 | 04/29/2016 | Serious | |
Penalty | C: Contested | 04/28/2016 | $0.00 | 04/29/2016 | Serious | |
Penalty | Z: Issued | 04/05/2016 | $0.00 | 04/29/2016 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience: 1) On January 13, 2016, and at prior times, ammonia detectors in the FES and Frick machinery rooms were not function tested on 3 month intervals between calibration, per the manufacturers recommendations and the employers mechanical integrity inspection procedures.