Violation Detail
Standard Cited: 19100106 D04 IV Flammable liquids.
Inspection Nr: 1106751.015
Citation: 01001B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $0.00
Issuance Date: 05/17/2016
Nr Instances: 1
Nr Exposed: 26
Abatement Date: 06/01/2016
Gravity: 5
Report ID: 0213600
Contest Date: 06/13/2016
Final Order: 11/23/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/23/2016 | $0.00 | 06/01/2016 | Serious | |
Penalty | C: Contested | 06/14/2016 | $2,800.00 | 06/01/2016 | Serious | |
Penalty | Z: Issued | 05/17/2016 | $2,800.00 | 06/01/2016 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.106(d)(4)(iv): The ventilating equipment and any lighting fixtures were not operated by the same switch located outside of the door. A pilot light was not installed adjacent to the switch when Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed within the room. a) Flammable Storage Room - On or about 11/19/15, the mechanical ventilation and the lighting fixtures were operated from separate switches. ABATEMENT CERTIFICATION REQUIRED