Violation Detail
Standard Cited: 19100107 B05 I Spray finishing using flammable and combustible materials.
Inspection Nr: 998078.015
Citation: 01001A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $3,250.00
Issuance Date: 04/01/2015
Nr Instances: 3
Nr Exposed: 4
Abatement Date: 03/30/2016
Gravity:
Report ID: 0627700
Contest Date: 04/02/2015
Final Order: 01/25/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/25/2016 | $3,250.00 | 03/30/2016 | Other | |
Penalty | C: Contested | 08/26/2015 | $5,000.00 | 04/16/2015 | Serious | |
Penalty | Z: Issued | 04/01/2015 | $5,000.00 | 04/16/2015 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.107(b)(5)(i): The spraying operations were not designed, installed and maintained so that the average air velocity over the open face of the booth was not less than 100 linear feet per minute. Visible gauges or audible alarm or pressure activated devices were not installed to indicate or insure that the required air velocity is maintained. Filter rolls were not inspected to insure proper replacement of filter media: On or about October 7, 2014, employees were exposed to the hazard of contact with hazardous chemicals and the hazard of fire due to the employer not ensuring: c) Filters in the spray booth were inspected to ensure proper replacement.