Powered by GoogleTranslate

Violation Detail

Standard Cited: 5A0001 OSH Act General Duty Paragraph

Inspection Nr: 304363559

Citation: 01001A

Citation Type: Serious

Abatement Status: X

Initial Penalty: $1,125.00

Current Penalty: $675.00

Issuance Date: 08/15/2003

Nr Instances: 1

Nr Exposed: 2

Abatement Date: 10/02/2003

Gravity: 03

Report ID: 0522500

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:

Substance: 8870


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 09/10/2003 $675.00 10/02/2003 Serious  
Penalty Z: Issued 08/15/2003 $1,125.00 10/02/2003 Serious  

Text For Citation: 01 Item/Group: 001A Hazard: ELECTRIC

Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a.Maintenance employees who routinely perform tasks such as equipment PM's (amperage draws), checking voltages at fuses and contacts, replacing fuses, replacing breakers, troubleshooting motors and checking (and replacing) power feed lines on die tip heater(s) were exposed to potential electrical hazards such as shock, burn, electrocution, arc flash, and arc blast, while working on energized electrical systems of up to 480 Volts. The employees did not wear all necessary electrical personal protective equipment such as face shields, safety glasses, and were not utilizing all the necessary specialized tools, barriers , shields or insulating materials to protect against all potential electrical hazards. No adequate hazard analysis (such as a flash hazard analysis as described in NFPA 70E ("Standard for Electrical Safety Requirements for Employee Workplaces" (2000 Edition) Section 2-1.3.3)) had been conducted to determine whether the potential hazards of the work to be performed (such as shock, electrocution, arc blast, and arc flash) warranted the use of any, or all such personal protective equipment, specialized tools, barriers, shields or insulating materials. Feasible means of abatement could have been achieved by conducting a Flash Hazard Analysis in accordance with NFPA 70E Section 2- 1.3.3 (or its equivalent) and providing for, and requiring, the use of the necessary personal protective equipment as determined following that analysis.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close