Powered by GoogleTranslate

Violation Detail

Standard Cited: 5A0001 OSH Act General Duty Paragraph

Inspection Nr: 300569563

Citation: 01001A

Citation Type: Serious

Abatement Status: I

Initial Penalty: $4,500.00

Current Penalty: $2,250.00

Issuance Date: 03/22/2000

Nr Instances: 1

Nr Exposed:

Abatement Date: 03/27/2000

Gravity: 10

Report ID: 0523300

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty I: Informal Settlement 04/05/2000 $2,250.00 03/27/2000 Serious  
Penalty Z: Issued 03/22/2000 $4,500.00 03/27/2000 Serious  

Text For Citation: 01 Item/Group: 001A Hazard: ELECTRIC

Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: On December 3, 1999, employees making organic castings or paints and using flammable and combustible liquids in the 3rd floor, plant 1 manufacturing room were exposed to fires and explosions in that electrical switch gear (ignition sources) located in the north west enclosure or room was not safeguarded by positive pressure ventilation designed to prevent entry of flammable vapors, that is, the ventilation system was inoperable. Also, when the positive pressure fails or is not maintained, the protective enclosure was not provided with an alarm or indicator which shall warm the user to take action or shall automatically de-energize the power from ignition, capable equipment. "AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT METHOD TO CORRECT THIS HAZARD IS...." These hazards is to design and construct the enclosure, electrical equipment and switch gear using positive pressure ventilation that is maintained by devices such as alarms, indicators, cut-offs or interlock switch which warn the user to take action or shall automatically de-energize power from ignition-capable equipment as stipulated by NFPA 35, standard for the manufacture of organic coatings 1995, chap 3-6.4 and NFPA 496 standard for purged and pressurized enclosures for electrical equipment, 1998, chapter 2-3.2.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.