Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100106 D04 I Flammable liquids.

Inspection Nr: 1861490.015

Citation: 01001A

Citation Type: Serious

Abatement Status: Abatement Completed

Initial Penalty: $8,511.00

Current Penalty: $8,511.00

Issuance Date: 01/22/2026

Nr Instances: 1

Nr Exposed: 80

Abatement Date: 04/30/2026

Gravity: 5

Report ID: 0134000

Contest Date:

Final Order: 02/24/2026

Related Event Code (REC): C

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty A: Amendment 06/11/2026 $8,511.00 04/30/2026 Serious  
Penalty I: Informal Settlement 02/24/2026 $4,000.00 04/30/2026 Serious  
Penalty Z: Issued 01/22/2026 $8,511.00 02/26/2026 Serious  

Text For Citation: 01 Item/Group: 001A Hazard:

29 CFR 1910.106(d)(4)(i):Inside flammable or combustible liquid storage room(s) were not constructed to meet the required fire-resistive rating as specified in NFPA 251-1969: Location: Warehouse B, Room 141 a) On or about 11/25/25, the employer did not ensure that a flammable or combustible liquid storage room was constructed to meet NFPA 251-1969, in that the floor was not provided with a liquid-tight sill or ramp. Both category 2 and category 3 flammable materials were stored within the room.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.