Violation Detail
Standard Cited: 19100029 B01 Fall protection systems and falling object protection-criteria and practices.
Inspection Nr: 1831476.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $10,129.00
Current Penalty: $10,129.00
Issuance Date: 09/10/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 10
Report ID: 0111100
Contest Date: 11/14/2025
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 12/01/2025 | $10,129.00 | Serious | ||
| Penalty | Z: Issued | 09/10/2025 | $10,129.00 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.29(b)(1): The top edge height of the top rail was not installed at 42 inches plus or minus 3 inches, above the walking-working surface: ND Paper, Cogen #7 Boiler, 9th Level North Access - The top edge height of the top rail was approximately 34 inches above the walking-working surface. The fall distance was greater than 80 feet.