Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1803784.015
Citation: 01001A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $16,550.00
Current Penalty: $11,585.00
Issuance Date: 07/01/2025
Nr Instances: 2
Nr Exposed: 2100
Abatement Date: 08/18/2025
Gravity: 10
Report ID: 0830500
Contest Date:
Final Order: 08/04/2025
Related Event Code (REC): C
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/04/2025 | $11,585.00 | 08/18/2025 | Other | |
Penalty | Z: Issued | 07/01/2025 | $16,550.00 | 08/18/2025 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(3)(i)(B):The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process: Cargill, Inc. DBA Cargill Meat Solutions Corporation, 1505 East Burlington Avenue Fort Morgan, CO 80701: On or about February 10, 2025, employees were exposed to inhalation hazards associated with ammonia from the following conditions: (a) The employer did not maintain accurate piping and instrument diagrams (P&ID) for the liquid header piping. The P&ID for the sub-roof containing the liquid header was missing a Henry Technology Pressure Relief Valve (serial number 1422, category 5602, size ? inch, set PSI 250, capacity 57.7). (b) The employer did not maintain accurate piping and instrument diagrams (P&ID) for the liquid header piping. The P&ID for the sub-roof containing the liquid header was missing a Henry Technology Pressure Relief Valve (serial number 1419, category 5602, size ? inch, set PSI 250, capacity 57.6).