Violation Detail
Standard Cited: 19100106 B01 I B Flammable liquids.
Inspection Nr: 1750423.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $8,065.50
Issuance Date: 11/06/2024
Nr Instances: 2
Nr Exposed: 10
Abatement Date: 12/26/2024
Gravity: 10
Report ID: 0524200
Contest Date:
Final Order: 12/06/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/06/2024 | $8,065.50 | 12/26/2024 | Serious | |
Penalty | Z: Issued | 11/06/2024 | $16,131.00 | 12/11/2024 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.106(b)(1)(i)(b): Tanks located above ground or inside buildings were not of noncombustible construction. (a) On or about May 23, 2024, the employer utilized a tank, P-7, constructed of glass-fiber-reinforced thermoset resin, a combustible material, as the mixing and storage tank for a Category 3 Flammable liquid in an amount exceeding 3800 gallons. (b) On or about May 22, 2024, the employer utilized a tank, P-6, constructed of glass-fiber-reinforced thermoset resin, a combustible material, as the mixing and storage tank for a Category 3 Flammable liquid in an amount exceeding 7600 gallons. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement or other written records.