Violation Detail
Standard Cited: 19100110 B06 II Storage and handling of liquefied petroleum gases.
This violation item has been deleted.
Inspection Nr: 1705479.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $0.00
Issuance Date: 01/11/2024
Nr Instances: 2
Nr Exposed: 10
Abatement Date: 01/31/2024
Gravity: 10
Report ID: 0936200
Contest Date:
Final Order: 01/25/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/25/2024 | $0.00 | 01/31/2024 | Serious | |
Penalty | Z: Issued | 01/11/2024 | $15,625.00 | 01/31/2024 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.110(b)(6)(ii): Each individual container was not located the minimum specified distance from an important building or group of buildings in accordance to Table H-23: 25 ft for aboveground tanks with 500 - 2,000 gallons capacity. On and/or before October 23, 2023, the employer did not ensure that the propane tanks used for their laundry equipment was properly distanced from the facility itself. Employees were potentially exposed to fire and/or explosion hazard(s) in the following locations: a) Patio Area Tank b) Vaporizer Tank