Violation Detail
Standard Cited: 19100094 B04 II Ventilation.
Inspection Nr: 1694067.015
Citation: 01001A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $11,524.00
Current Penalty: $0.00
Issuance Date: 02/21/2024
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 03/18/2024
Gravity: 5
Report ID: 0627700
Contest Date: 03/13/2024
Final Order: 12/06/2024
Related Event Code (REC):
Emphasis:
Substance: 0689
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 12/06/2024 | $0.00 | 03/18/2024 | Other | |
| Penalty | C: Contested | 04/12/2024 | $11,524.00 | 03/18/2024 | Serious | |
| Penalty | Z: Issued | 02/21/2024 | $11,524.00 | 03/18/2024 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.94(b)(4)(ii): Exhaust systems for grinding, polishing, and buffing operations were not tested in the manner described in American Standard Fundamentals Governing the Design and Operation of Local Exhaust Systems, Z9.2-1960: On or about October 24, 2023, at the bonded panel sanding booth, an employee used an air powered sanding tool in the booth to sand primed panels and the air was not tested at the discharge of the booth's air-cleaning device. The back exterior of the booth had accumulations of green dust containing chromium (VI) which exposed employees to chromium (VI).