Violation Detail
Standard Cited: 19100106 D05 V Flammable liquids.
Inspection Nr: 1639694.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $61,391.00
Current Penalty: $15,625.00
Issuance Date: 02/17/2023
Nr Instances: 1
Nr Exposed: 69
Abatement Date: 03/10/2023
Gravity: 5
Report ID: 0522000
Contest Date: 03/17/2023
Final Order: 06/21/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/21/2023 | $15,625.00 | 03/10/2023 | Serious | |
Penalty | C: Contested | 03/17/2023 | $61,391.00 | 03/10/2023 | Repeat | |
Penalty | Z: Issued | 02/17/2023 | $61,391.00 | 03/10/2023 | Repeat |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.106(d)(5)(v): "General purpose public warehouses." Storage shall be in accordance with Table H-14 or H-15 and in buildings or in portions of such buildings cut off by standard firewalls. Material creating no fire exposure hazard to the flammable liquids may be stored in the same area. On or about December 14, 2022, flammable liquids were stored in an unprotected storage not in accordance with Table H-14 or H-15 in that: a.) The Acrylic Resin, (89) 50-gallon drums of Category 3 flammable liquid totaling 4,450 gallons; the T-Butyl Acetate, (19) 55-gallon drums of Category 2 flammable liquid totaling 1,045 gallons; the Roskydal 500A, (15) 55-gallon drums of Category 3 flammable liquid totaling 825 gallons; the Solvent Methyl Ethyl Ketone, (2) 275-gallon totes of Category 2 flammable liquid totaling 550 gallons; the Reclaim Solvent, (26) 55-gallon drums of Category 2 flammable liquid totaling 1,430 gallons; the Suspenso 201K, (8) 55-gallon drums of Category 3 flammable liquid totaling 440 gallons, the Derakane, (5) 55-gallon drums of Category 3 flammable liquid totaling 275 gallons; the Derakane (4) partial 55-gallon drums of Category 3 flammable liquid; the Xylene, (9) 53-gallon drums of Category 3 flammable liquid totaling 477 gallons; the Reclaim Solvent, (8) 55-gallon drums of Category 2 flammable liquid totaling 440 gallons; the Desmopen, (5) 55-gallon drums of Category 3 flammable liquid totaling 275 gallons; and the Solvent Methyl Ethyl Ketone, (1) partial 55-gallon drum of Category 2 flammable liquid was stored in the Hanger Room. b.) The B65T604 Acrolon 218 HS Polyurethane - Gloss Part A, (5) partial 309-gallon totes of Category 2 flammable liquid totaling 1,512 gallons was stored at Column F13. c.) The B65T354 Hi-Solids Polyurethane Semi-Gloss Part S Ultradeep/Clear Tint Base, (11) partial 50-gallon drums of Category 3 flammable liquid totaling 455-gallons; the B65W351 Hi-Solids Polyurethane Semi-Gloss Part S Extra White/Tint Base, (6) partial 50-gallon drums of Category 3 flammable liquid totaling 265-gallons; the B65T304, (4) partial 50-gallon drums of Category 3 flammable liquid totaling 171-gallons; the B65W651 Acrolon 218 HS Polyurethane Semi-Gloss Part A Extra White/Tint Base, (17) partial 50-gallon drums of Category 2 flammable liquid totaling 860-gallons was stored between Columns F12-F11. The Sherwin-Williams Company, General Polymers, The Sherwin Williams High Performance Flooring was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.106(d)(5)(v), which was contained in OSHA inspection number 1576119 , citation number 1, item number 1a and was affirmed as a final order on June 10, 2022, with respect to a workplace located at The Sherwin-Williams Company, General Polymers, The Sherwin Williams High Performance Flooring, 145 Caldwell Drive, Cincinnati, OH 45216.