Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1533515.015
Citation: 01001A
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $9,753.00
Current Penalty: $3,600.00
Issuance Date: 10/08/2021
Nr Instances: 1
Nr Exposed: 600
Abatement Date: 12/15/2021
Gravity: 5
Report ID: 0134000
Contest Date: 11/01/2021
Final Order: 11/10/2021
Related Event Code (REC):
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/10/2021 | $3,600.00 | 12/15/2021 | Other | |
Penalty | C: Contested | 11/01/2021 | $9,753.00 | 11/15/2021 | Serious | |
Penalty | Z: Issued | 10/08/2021 | $9,753.00 | 11/15/2021 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process: (a) Location - 330 Ballardvale Street, Wilmington, MA: On or about May 27, 2021, the three way valve installed in conjunction with the pressure relief valves protecting the ammonia refrigeration system's high pressure receiver was depicted as a normally closed angle valve and an unidentified symbol on PID08 High Pressure Receiver V-1.