Violation Detail
Standard Cited: 19100106 E06 I Flammable liquids.
Inspection Nr: 1436294.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,934.00
Current Penalty: $7,757.00
Issuance Date: 01/07/2020
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 02/04/2020
Gravity: 10
Report ID: 0524530
Contest Date:
Final Order: 01/22/2020
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/22/2020 | $7,757.00 | 02/04/2020 | Serious | |
Penalty | Z: Issued | 01/07/2020 | $11,934.00 | 02/04/2020 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: A) On or about October 7, 2019, the employer did not ensure precautions were taken to prevent filling liquid propane gas containers while the container was on or near an ignition source. LPG cylinders were filled while housed inside or on top of PIVs, which were parked approximately five (5) feet away from the LPG dispensing station. B) On or about October 7, 2019, the employer did not ensure flammable vapor source was controlled by permitting fuel station valves to remain open when an attendant was not present.