Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1334070.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,260.00
Current Penalty: $9,945.00
Issuance Date: 01/25/2019
Nr Instances: 2
Nr Exposed: 36
Abatement Date: 02/25/2019
Gravity: 10
Report ID: 0523300
Contest Date:
Final Order: 02/20/2019
Related Event Code (REC): A;R
Emphasis:
Substance: 0170
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/20/2019 | $9,945.00 | 02/25/2019 | Serious | |
| Penalty | Z: Issued | 01/25/2019 | $13,260.00 | 02/25/2019 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On or about July 30, 2018, the employer did not document that the equipment associated with the anhydrous ammonia refrigeration system complied with recognized and generally accepted good engineering practices, such as but not limited to, IIAR Bulletin No. 109 - 1997 "IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System" in that fan mounting brackets for evaporative condensers and blast freezer tunnels were not being inspected for vibration.
Translate