Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1295794.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,054.00
Current Penalty: $12,934.00
Issuance Date: 07/13/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 10/31/2018
Gravity: 10
Report ID: 0626700
Contest Date:
Final Order: 08/15/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/15/2018 | $12,934.00 | 10/31/2018 | Serious | |
Penalty | Z: Issued | 07/13/2018 | $9,054.00 | 08/29/2018 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. (a) Dianal America Inc facility: On February 12 2018 and at times prior to, the employer did not document that the facility siting of the control room complied with Recognized and Generally accepted Good Engineering Practices (RAGAGEP) when the employer failed to do any of the following; (I) Conduct building siting evaluations for existing buildings intended for occupancy (II) Evaluate how the control room could be impacted in the event of a blast (III) Evaluate how the control room could be impacted by flammable vapor release. This condition exposed employees to fire and explosion hazards. (Example RAGAGEP for facility siting include, but not limited to API 752, paragraph 5.4,6.6 and 7.4)