Violation Detail
Standard Cited: 19100106 E06 I Flammable liquids.
Inspection Nr: 1270859.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,054.00
Current Penalty: $4,622.00
Issuance Date: 02/27/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 03/30/2018
Gravity: 10
Report ID: 0112300
Contest Date:
Final Order: 03/23/2018
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/23/2018 | $4,622.00 | 03/30/2018 | Serious | |
Penalty | Z: Issued | 02/27/2018 | $9,054.00 | 03/15/2018 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: (a) Batch making room: On or about October 16, 2017 and at times prior thereto employees used a Blue Hawk metal ice scraper, which is capable of producing sparks, in conjunction with Acetone, a flammable liquid, to perform floor cleaning operations. (b) Batch making room: On or about October 16, 2017 and at times prior thereto employees handled Abeita HC-85, which is capable of producing static charges when poured, into process vessels containing flammable liquids, without taking adequate precautions to prevent static electrical charges from developing, which could cause ignition of the flammable liquid.