Violation Detail
Standard Cited: 19100304 B03 II B Wiring design and protection.
Inspection Nr: 1249090.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $11,408.00
Current Penalty: $8,000.00
Issuance Date: 09/05/2017
Nr Instances: 1
Nr Exposed: 8
Abatement Date:
Gravity: 10
Report ID: 0111500
Contest Date:
Final Order: 10/03/2017
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/03/2017 | $8,000.00 | Serious | ||
| Penalty | Z: Issued | 09/05/2017 | $11,408.00 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.304(b)(3)(ii)(B): Receptacles other than 125 volt, single-phase, 15-, 20-, and 30-ampere receptacles that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. WORKSHOP/CELL No. 6: The black flexible cord of the No. 2 Stake of the No. 27 Air Press, unknown identification, was not plugged into a safely working Ground Fault Circuit Interrupter (GFCI) for appropriate and safe protection for all personnel at all times. On/or about July 24, 2017, the above GFCI had suddenly tripped when both hands of the operator were in the point-of-operation while performing normal tasks, and the upper ram/die landed on both hands of the operator. The operator sustained very severe crushing/smashing/amputation to the fingers on both hands from the incident.