Violation Detail
Standard Cited: 19100147 C04 II B The control of hazardous energy (lockout/tagout).
Inspection Nr: 1211730.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,675.00
Current Penalty: $8,872.00
Issuance Date: 08/04/2017
Nr Instances: 1
Nr Exposed: 30
Abatement Date: 08/10/2017
Gravity: 10
Report ID: 0111100
Contest Date:
Final Order: 08/24/2017
Related Event Code (REC): R
Emphasis:
Substance: 0614
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/24/2017 | $8,872.00 | 08/10/2017 | Serious | |
| Penalty | Z: Issued | 08/04/2017 | $12,675.00 | 08/10/2017 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedure did not clearly and specifically identify all specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy: Bleach Plant - On or about February 16, 2017, the lockout procedure for the Bleach Plant Scrubber did not identify the scrubber bypass valve which needed to be partially opened before the manhole cover was removed. Failure to open the scrubber bypass valve resulted in the release of chlorine dioxide.