Violation Detail
Standard Cited: 19100106 D04 I Flammable liquids.
Inspection Nr: 1106751.015
Citation: 01001A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,500.00
Current Penalty: $1,032.50
Issuance Date: 05/17/2016
Nr Instances: 1
Nr Exposed: 26
Abatement Date: 06/17/2016
Gravity: 5
Report ID: 0213600
Contest Date: 06/13/2016
Final Order: 11/23/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/23/2016 | $1,032.50 | 06/17/2016 | Serious | |
Penalty | C: Contested | 06/14/2016 | $3,500.00 | 06/17/2016 | Serious | |
Penalty | Z: Issued | 05/17/2016 | $3,500.00 | 06/17/2016 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised seal or ramp at least 4 inches in height. Opening(s) from inside flammable and combustible storage room(s) were not provided with approved self-closing fire doors. The inside flammable and combustible storage room(s) were not liquid-tight where the walls joined the floor: a) Flammable storage room - On or about 11/19/15, the flammable storage room where 55 gallon drums of resins having flash points ranging from 84 deg F to 89 deg F, and 5-gallon buckets of coatings with flash points ranging from 68.5 deg F to 82 deg F were stored was a room off of the manufacturing area having a floor the same height as the rest of the building. It was not provided with an self-closing door, nor was the room liquid-tight where the walls joined the floor. ABATEMENT CERTIFICATION REQUIRED