Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 980125.015
Citation: 01001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $3,300.00
Current Penalty: $2,310.00
Issuance Date: 08/13/2014
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 08/20/2014
Gravity:
Report ID: 0419400
Contest Date:
Final Order: 09/08/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/08/2014 | $2,310.00 | 08/20/2014 | Other | |
| Penalty | Z: Issued | 08/13/2014 | $3,300.00 | 08/20/2014 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) Slot 47 (5841) - On or about June 11, 2014 employees were exposed to electric shock hazards while working near a 480V disconnect box with a 1 and 3/16 inch hole in the sidewall. The hole was not effectively closed. (b) Maintenance Shop - On or about June 11, 2014 employees were exposed to electric shock hazards while working near a 480V to 240V transformer with 2 holes in the sidewall over 2 inches in diameter. The holes were not effectively closed.