Violation Detail
Standard Cited: 19100106 D04 III Flammable liquids.
Inspection Nr: 904561.015
Citation: 01001
Citation Type: Serious
Abatement Date: 04/01/2014 2
Initial Penalty: $5,000.00
Current Penalty: $3,000.00
Issuance Date: 06/10/2013
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0111500
Contest Date:
Final Order: 06/26/2013
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | $3,000.00 | 04/01/2014 | Serious | ||
Penalty | I: Informal Settlement | 06/26/2013 | $3,000.00 | 11/04/2013 | Serious | |
Penalty | Z: Issued | 06/10/2013 | $5,000.00 | 07/05/2013 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(d)(4)(iii): Wiring. Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use. Barrel Storage Area (BSA): The electrical wiring and equipment, located and installed inside the BSA that was used to store hazardous waste flammable liquids were neither intrinsically safe nor approved for Class 1 Division II Hazardous Location.